Yaskawa Error Code A910 Exclusive
Once the physical cause is resolved or parameters are corrected:
Summary Checklist:
DC Bus / Rectifier Issues
Load Related (High inertia + short decel) yaskawa error code a910 exclusive
| Step | Action | Expected Result | | :--- | :--- | :--- | | 1 | Monitor U1-07 (DC Bus Voltage) during normal run. | Should be ~1.35x input voltage (e.g., 540-620VDC for 400V class, 270-310VDC for 200V class). | | 2 | Check L2-05 (Undervoltage detection level). Factory default is usually 380VDC (400V class). If set too high, nuisance A910 occurs. | Lower L2-05 by 5-10% only if power supply is truly unstable. | | 3 | Check L2-01 (Momentary Power Loss Ride-Thru Time). Default = 1.0 sec. | Increase to 2.0 seconds if utility sags are common. | | 4 | Measure input voltage while running at 100% load. | Voltage drop should not exceed 10% from no-load to full-load. | Once the physical cause is resolved or parameters
To avoid the exclusivity of an A910 shutdown: Summary Checklist: